Change Language
Hot Water Circulation System

Hot Water Circulation System

Product Details:

  • Type Hot Water Circulation System
  • Color Silver/Grey/Red
  • Click to View more
X

Hot Water Circulation System Price And Quantity

  • 1 Unit

Hot Water Circulation System Product Specifications

  • Silver/Grey/Red
  • Hot Water Circulation System

Hot Water Circulation System Trade Information

  • 10 Unit Per Month
  • 10-15 Days

Product Description

We are engaged in offering 3 Pass Thermic Fluid Heaters to our clients from all over the world. Our 3 Pass liquid phases thermic fluid heaters offer high thermal efficiency. These are available in different capacities as well as specifications to suit the exact requirements of the clients. Equipped with fluid pipelines, storage tanks etc. these can be easily installed. We provide these at the most competitive prices.

We are one of the preeminent manufacturers and exporters of Thermic Fluid Heaters in the market. We are able to offer Thermic Fluid Heaters, which are energy efficient and work on liquid & vapor phase. Known for longer working life, these can be used with gas, oil, coal and agro-waste fuels. Our precision engineered Thermic Fluid heaters are robust in construction and require less maintenance costs as compared to conventional heaters. We offer Thermic Fluid Heaters in a variety of sizes and can also customize them according to the client.

Characteristics
  • Heat transfer efficiency
  • Long thermic fluid life
  • Corrosion free
  • No scale problems
  • No boiler regulation
  • High temperature
  • Abrasion resistant
  • Easy to use

Consists of
  • Fully automatic burner
  • High temperature re-circulating pumps
  • Advanced safety features
  • Complete control panel

 Specifications

Abnormal Condition

Safety Action

Low Thermic Fluid Level in Expansion Tank

Level Switch actuated at expansion tank cuts of the ID Fan / FD Fan.

Low Thermic Fluid Flow

Differential pressure switch (DPS) across inlet and outlet headers cuts of the ID Fan slowing down combustion

Thermic Fluid system pressure high due to system valves closure etc.

Pressure switch cuts of ID Fan and alarm. Safety relief valve (Optional) to be provided in the system piping so as to by pass the oil.

Thermic Fluid Temperature High

Digital Temperature cuts of ID fan at set point

 

 

Coil Chocking

Differential pressure Switch (DPS) across system cuts of the ID Fan Slowing down combustion

 

 

Thermic Fluid Motor Trip

Electrical Interlock cuts of fans

 

 

Power Failure

Diesel Engine (Optional) keeps thermic fluid moving to avoid overheating and overflow of oil. Exhaust with Damper provided on furnace to drive away hot gases directly.

  

Enter Buying Requirement Details